Separate isokinetic EPA Method 13A and heated cascade impactor tests were performed on three cooling towers before and after drift eliminator modifications. The modifications consisted of installation of Munters D-15 eliminators over the existing eliminators. The reduction of drift and corresponding mineral mass emissions was about 80%.

92-10: Reduction of Cooling Tower PM10 Emissions Due to Drift Eliminator